Skip to content
Back to products
D-Cube-H125/261
Commercial and Industrial Energy Storage Cabinet

D-Cube-H125/261

  • Integrated PV & Storage Efficiency
    • Integrated PV and storage with a single PV array capacity up to 2x the inverter rated power
    • Supports 10 MPPTs and 20 inputs, flexibly adapting to complex rooftop scenarios
    • Supports parallel connection of up to 10 inverters with strong system scalability
  • Safe & Reliable Protection
    • Independent battery cluster design eliminates inter-cluster circulating current for higher safety redundancy
    • Pack + Cabinet-level aerosol and water fire protection in three tiers
    • IP55 and C4 corrosion resistance ratings, supporting harsh outdoor environments from -25 to +55°C
  • Seamless Backup Switching
    • On/off-grid switching time less than 10ms, ensuring uninterrupted power to critical loads
    • Supports 1.6x rated power short-term overload capability for 200ms
    • 92% high depth of discharge for greater usable capacity
  • Smart & User-Friendly O&M
    • Supports real-time APP monitoring and remote OTA upgrades
    • Compatible with automatic diesel generator start/stop, with configurable self-consumption and peak-valley arbitrage modes
    • Supports multiple communication interfaces including CAN, RS485, Ethernet, Wi-Fi, and cellular

Specifications

Battery Parameters
Battery TypeLithium Iron Phosphate (LFP)
Cell Capacity3.2/314V/Ah
Cell Configuration1P260S
Nominal Capacity261.24kWh
Nominal Voltage832V
Voltage Range728-941.2Vdc
Max Charge/Discharge Current160A
Depth of Discharge (DOD)92%
Cooling MethodLiquid Cooling
Battery Pack Fire SuppressionAerosol
Battery Cluster DesignIndependent battery cluster design to prevent circulating current
Electrical Parameters
Recommended Max PV Array Capacity250kW
Max Input Voltage (PV Side)1000V
Nominal Input Voltage (PV Side)600V
Startup Voltage180V
MPPT Voltage Range150-950V
Max Input Current10*42A
Max Short-Circuit Current10*60A
Number of MPPTs / Max Input Strings10/20
Nominal Output Power (On-Grid)125kW
Max Apparent Output Power (On-Grid)125kVA
Nominal Grid Voltage3/N/PE, 230/400 or 3/N/PE, 220/380V
Nominal Grid Frequency50/60Hz
Nominal Grid Output Current180.4/189.9A
Power Factor> 0.99 (adjustable from 0.8 leading to 0.8 lagging)
Current Harmonic Distortion (THDi)< 3%
Nominal Output Power (Off-Grid Backup)125kW
Max Apparent Output Power (Off-Grid Backup)1.2x rated power for 100s; 1.4x rated power for 10s; 1.6x rated power for 200ms
On/Off-Grid Switching Time<10ms
Backup Nominal Grid Voltage3/N/PE, 230/400 or 3/N/PE, 220/380V
Backup Nominal Frequency50/60Hz
Voltage Harmonic Distortion (THDv, Linear Load)≤2%
Mechanical Parameters
Dimensions (W×D×H)1180×1800×2200mm
Base Dimensions (W×D)1000×1350mm
Weight2.62t
Protection RatingIP55
Anti-Corrosion RatingC4
Environmental Parameters
Operating Temperature-25~+55 (derating at ≥45°C)℃
Relative Humidity≤95%
Altitude≤4000 (derating at ≥2000m)m
Protection
System Fire SuppressionBattery pack aerosol + cabinet water-based fire suppression interface (three-level fire protection)
Battery Pack Fire SuppressionAerosol
Cabinet Fire Suppression InterfaceWater-based fire suppression interface
Battery Management System (BMS)Advanced BMS with multi-point sampling and real-time data feedback
PCS Cooling MethodAir Cooling
Communication
Communication InterfaceCAN, RS485, Ethernet, Wi-Fi (optional), Cellular (optional), LAN (optional)
Communication ProtocolSupports corresponding protocols for the above interfaces (optional)
Display
Monitoring MethodReal-time monitoring via mobile APP, supports remote OTA upgrade
Efficiency
Current Harmonic Distortion (On-Grid)< 3%
Power Factor (On-Grid)> 0.99
Voltage Harmonic Distortion (Off-Grid, Linear Load)≤2%
Certifications & Standards
Protection Rating StandardIP55
Anti-Corrosion Rating StandardC4
Version Information
Datasheet Version1.4