Commercial and Industrial Energy Storage Cabinet
EFIS-D-W50/100-AIO
- Ultimate Safety
- Three-level fire protection: Pack and cluster cabinet-level aerosol + water spray multi-layer protection
- Innovative BMS technology with fine-grained sampling, real-time cell health monitoring and alarming
- Standard AFCI arc fault protection, AC & DC dual-side secondary surge protection
- High-Density Integration
- Factory-pre-assembled integrated design, no on-site commissioning required, ready to use out of the box
- Uses 280Ah high energy density cells, supporting 140A high-current charge and discharge
- Integrated AC-DC architecture, supporting multi-unit off-grid parallel connection with DC coupling
- Flexible & Efficient
- 4 MPPT channels, supporting 200% PV oversizing, wide voltage range of 150-850V
- 20ms seamless off-grid switching, ensuring uninterrupted power supply for critical loads
- Supports multiple revenue scenarios including self-consumption, peak-valley arbitrage, and backup power
- Smart Collaboration
- APP real-time monitoring of system status, remote OTA upgrade for continuous strategy optimization
- Intelligent backup power coordination with diesel generators, automatic switching without manual intervention
- Supports multiple communication interfaces including CAN/RS485/Ethernet/Wi-Fi/Cellular
Specifications
Basic Parameters
| Battery Type | LFP (Lithium Iron Phosphate) |
| Cell Capacity | 3.2V/Ah |
| Cell Capacity | 280Ah |
| Cell Configuration | 1P112S |
| Nominal Energy | 100.35kWh |
| Nominal Voltage | 358.4V |
| Voltage Range | 280~408.8V |
| Max Charge/Discharge Current | 140A |
| Depth of Discharge | 95% |
| Cooling Method | Fan cooling |
| Temperature Control Method | Industrial air conditioner |
| Hybrid Nighttime Self-Consumption | <25W |
Electrical Parameters
| Recommended Max Input Power | 100kW |
| Max DC Input Voltage | 1000V |
| Nominal DC Input Voltage | 600V |
| Start-up Voltage | 180V |
| MPPT Voltage Range | 150-850V |
| Number of MPPTs | 4 |
| Max Input Current | 4X40A |
| Max Short-Circuit Current | 4X60A |
| Max Number of Input Strings | 8 |
| Nominal AC Output Power (On-grid) | 50kW |
| Max Apparent Output Power (On-grid) | 50kVA |
| Nominal Grid Voltage | 3/N/PE, 220/380, 230/400V |
| Nominal Grid Frequency | 50/60Hz |
| Max Output Current | 76/72.2A |
| Power Factor | >0.99 (0.8 leading ~ 0.8 lagging) |
| Current Harmonic THDi | <3 (at rated output power)% |
| Nominal AC Output Power (Off-grid) | 50kW |
| Max Apparent Output Power (Off-grid) | 1.6 times rated power, lasting 2s |
| Off-grid Switching Time | <20ms |
| Nominal Output Voltage (Off-grid) | 3/N/PE, 380/400V |
| Nominal Output Frequency (Off-grid) | 50/60Hz |
| Voltage Harmonic THDv | <3 (under linear load)% |
Mechanical Parameters
| Dimensions (W×D×H) | 1570×1280×1813mm |
| Base Dimensions (W×D×H) | 1200×1050×100mm |
| Weight | 1.3t |
Environmental Parameters
| Protection Rating | IP55 |
| Anti-Corrosion Rating | C4 |
| Operating Temperature | -20~+50 (load derating above 50)℃ |
| Relative Humidity | ≤95% |
| Altitude | ≤3000m |
Communication
| Communication Protocol | CAN, RS485, Ethernet, Wi-Fi (optional), Cellular network (optional), LAN (optional) |
| Communication Interface | RJ45 |
Efficiency
| PV Oversizing Ratio | Supports 200% PV oversizing |
Version Information
| Datasheet Version | 2.0 |