Enjoy
EPCS125-AM(-F)
- Cost Reduction & Efficiency
- Perfectly matched with 280/314/320Ah cell systems
- High power density, high conversion efficiency, zero battery loss, efficient and flexible
- Smart Control
- High-efficiency intelligent variable-speed fan control for better heat dissipation
- Smart allocation, flexible operation in multiple modes
- Efficient & Flexible
- Cluster-level management, three-phase three-wire/four-wire adaptive (enabled)
- Modular design, ultra-simple installation and O&M
- Intelligent & User-friendly
- Supports EMS and BMS system linkage and active power quality management
- Real-time monitoring, real-time fault warning and fault location
Specifications
DC-side Basic Parameters
| Operating Voltage Range (DC-side) | 615V~950V/650V~950V |
| Maximum Current (DC-side) | 203A |
AC-side Electrical Parameters
| Rated Voltage (AC-side) | 400V |
| Rated Voltage Range (AC-side) | ±15% |
| Rated Frequency | 50/60Hz |
| Wiring Method | Three-phase three-wire / Three-phase four-wire |
| Maintenance Method | Front wiring / Rear wiring |
| Rated Power | 125kW |
| Maximum Power | 138kW |
| Maximum Current (AC-side) | 200A |
| Power Factor | 0.99 / -1 ~ 1 |
| Current Distortion Rate | < 2% (at rated power) |
| DC Component | < 0.5% |
| Overload Capability | 110% long-term |
| Maximum Efficiency | 99% |
Mechanical Parameters
| Dimensions (W×H×D) | 520×232×785mm |
| Dimensions (W×H×D, Rear Wiring) | 520×232×725mm |
| Weight | 72kg |
| Weight (Rear Wiring) | 69kg |
Environmental Parameters
| Altitude | 4000m (derating required above 2000m) |
| Operating Temperature | -30℃~60℃ (derating required above 45℃) |
| Humidity | 5%RH~95%RH, non-condensing |
| Cooling Method | Smart air cooling |
| Protection Rating | IP20 |
Communication
| Communication Method | CAN/RS485/Ethernet |
Version Information
| Version | 1.3 |