Containerized Energy Storage
D-Ocean-5016D
- Intelligent Safety Protection
- Patented ICCS safety valve detection system for proactive early warning
- Thermal runaway confirmed in just 30–60 seconds, with 30-second rapid response
- Supports dual fire suppression with aerosol and water spray for precise extinguishing
- High-Density Integration
- Single cabinet capacity of 5MWh, integrating 12×416S1P large-capacity systems
- Supports series-parallel and back-to-back installation to save footprint
- Modular design for flexible expansion, reducing project costs
- Wide Temperature Range Stability
- Operating temperature range from -30°C to +55°C, reliable in all environments
- Liquid cooling temperature control technology keeps cell temperature difference ≤3°C, slowing degradation
- Suitable for applications up to 4000 meters altitude, with optional C4/C5 corrosion protection
- Smart Interconnectivity
- Supports multiple protocols including Modbus TCP, CAN2.0, and IEC61850
- Provides rich communication interfaces including Ethernet, RS485, and CAN
- Voltage acquisition accuracy ≤±3mV for precise battery status monitoring
Specifications
Electrical Parameters
| Cell Type | LFP 314Ah |
| System Battery Configuration | 12×416S1P |
| Nominal Capacity | 5MWh |
| Nominal Voltage | 1331.2Vdc |
| Operating Voltage Range | 1164.8~1500.0Vdc |
| Nominal Charge/Discharge Rate | 0.5P |
| System Cycle Efficiency | Max. 94% |
| Voltage Acquisition Accuracy | ≤±3mV |
Mechanical Parameters
| Dimensions (W×D×H) | 6058*2438*2896mm |
| Weight | 45t |
Environmental Parameters
| Protection Level | IP55 |
| Anti-corrosion Level | C4, C5 optional |
| Operating Humidity Range | 0%~95% RH% |
| Operating Temperature Range | -30~+55℃ |
| Maximum Operating Altitude | 4000 (derating above 2000)m |
| Cooling Method | Liquid Cooling |
| Noise | 75dB@1mdB |
| Battery Temperature Difference | ≤3℃ |
Protection
| Safety Valve Detection System | Supported |
| Thermal Runaway Confirmation Time | 30–60s |
| Valve Opening Warning Time | 3–5min |
| Prediction Range | 3–6月 |
| Fire Extinguishing System | Aerosol/Perfluorohexanone (optional) + Water Spray |
Communication
| Communication Interface | Ethernet/RS485/CAN |
| Communication Protocol | Modbus TCP, Modbus RTU, CAN2.0, IEC61850, IEC104 |
Certifications & Standards
| Certifications | UL9540A (Pack) / UN38.3 / IEC 61000 / IEC 62477 / IEC 62619 / IEC 63056 |
Version Information
| Document Version | Version 2.2 |